EPA 608 Type III · Section 608 Regulations · Hard
Under EPA's definition, a low-pressure appliance uses a refrigerant with what saturation pressure at 104°F?
Answer: A. Below 45 psia.
- ABelow 45 psia.✓ Correct
- BBetween 170 and 355 psia.
- CBelow 15 psig.
- DBetween 45 and 170 psia.
Why A is right
40 CFR 82.152 defines a low-pressure appliance as one using a refrigerant with a liquid-phase saturation pressure below 45 psia at 104°F, such as R-11, R-123 or R-1233zd(E). Between 45 and 170 psia is medium-pressure, and 170 to 355 psia is high-pressure.
More Type III questions
- Which certification covers servicing a centrifugal chiller charged with R-1233zd(E)?
- Which of the following is considered a low-pressure refrigerant?
- At what pressure does the rupture disc on a low-pressure centrifugal chiller typically burst?
- Where is the rupture disc typically located on a low-pressure chiller?
- How is the rupture disc piped to safely vent refrigerant?
Go deeper with the study guide EPA 608 Type I vs Type II vs Type III: Which One Do You Need?, try the free 10-question test or browse all EPA 608 practice questions.