EPA 608 Exam Prep

EPA 608 Type III · Leak Repair Requirements · Hard

A chiller with a 1,000-lb full charge needs 50 lbs added, 73 days after the last addition. What is its annualized leak rate?

Answer: D. 25%.

  1. A5%.
  2. B10%.
  3. C20%.
  4. D25%.✓ Correct

Why D is right

Annualizing method: (50 ÷ 1,000) × (365 ÷ 73) × 100 = 0.05 × 5 × 100 = 25% per year. That is well above the 10% threshold for comfort cooling.

More Type III questions

Go deeper with the study guide AIM Act 2026: The HFC Leak Repair Rules for HVAC Techs, try the free 10-question test or browse all EPA 608 practice questions.

A practice question written for study, checked against 40 CFR Part 82, Subpart F. It is not an official EPA exam question, and this site is not affiliated with the U.S. EPA.