EPA 608 Type III · Recharging Techniques · Medium
Why is a low-pressure chiller introduced with refrigerant vapor before liquid refrigerant during the charging process?
Answer: C. To keep the water in the tubes from freezing
- ATo prevent liquid slugging in the compressor
- BTo avoid fractionating the zeotropic blend
- CTo keep the water in the tubes from freezing✓ Correct
- DTo purge non-condensables from the system
Why C is right
In a deep vacuum, liquid refrigerant entering the system would boil at a very low temperature, potentially freezing the water in the tubes and rupturing them. Vapor is charged first until the pressure is above the saturation pressure that matches 32°F, the freezing point of water.
More Type III questions
- Before charging liquid into a chiller, what must the system pressure be?
- Why must low-pressure chillers be designed to be completely airtight?
- R-123 is rated B1 under ASHRAE 34. What does that mean?
- Which HCFO refrigerant is replacing R-123 in new low-pressure chillers?
- A chiller with a 1,000-lb full charge needs 50 lbs added, 73 days after the last addition. What is its annualized leak rate?
Go deeper with the study guide A2L Refrigerants and the R-410A Transition: A Tech’s Guide, try the free 10-question test or browse all EPA 608 practice questions.