EPA 608 Type III · Recharging Techniques · Hard
Before charging liquid into a chiller, what must the system pressure be?
Answer: D. Above the saturation pressure at 32°F.
- AExactly 0 psig.
- BAt a deep vacuum of 500 microns.
- CEqual to the ambient atmospheric pressure.
- DAbove the saturation pressure at 32°F.✓ Correct
Why D is right
The pressure must correspond to a saturation temperature above 32F (0C) so the liquid doesn't freeze the tubes.
More Type III questions
- Why is a low-pressure chiller introduced with refrigerant vapor before liquid refrigerant during the charging process?
- Why must low-pressure chillers be designed to be completely airtight?
- R-123 is rated B1 under ASHRAE 34. What does that mean?
- Which HCFO refrigerant is replacing R-123 in new low-pressure chillers?
- A chiller with a 1,000-lb full charge needs 50 lbs added, 73 days after the last addition. What is its annualized leak rate?
Go deeper with the study guide A2L Refrigerants and the R-410A Transition: A Tech’s Guide, try the free 10-question test or browse all EPA 608 practice questions.