With post-1993 recovery equipment, what level is required before replacing the compressor on a 150-lb R-410A system?
Answer: B. 0 psig.
- A15 inches of mercury vacuum.
- B0 psig.✓ Correct
- C10 inches of mercury vacuum.
- D25 inches of mercury vacuum.
Why B is right
R-410A is a high-pressure refrigerant (170 to 355 psia at 104°F). Table 1 of 40 CFR 82.156 sets 0 psig for high-pressure appliances holding less than 200 lbs, with any recovery equipment; 10 inHg applies from 200 lbs up (4 inHg with pre-1993 equipment).