EPA 608 Type III · Dehydration & Evacuation · Medium
The Type III evacuation level of 25 mm Hg absolute equals about how many microns?
Answer: C. 25,000 microns.
- A2,500 microns.
- B250 microns.
- C25,000 microns.✓ Correct
- D500 microns.
Why C is right
1 mm Hg equals 1,000 microns, so 25 mm Hg absolute is about 25,000 microns. That is the recovery level; an evacuation to dehydrate a system before charging goes much deeper.
More Type III questions
- Why is a low-pressure chiller introduced with refrigerant vapor before liquid refrigerant during the charging process?
- Before charging liquid into a chiller, what must the system pressure be?
- Why must low-pressure chillers be designed to be completely airtight?
- R-123 is rated B1 under ASHRAE 34. What does that mean?
- Which HCFO refrigerant is replacing R-123 in new low-pressure chillers?
Go deeper with the study guide EPA 608 Evacuation Levels: The Required Vacuum by Appliance, try the free 10-question test or browse all EPA 608 practice questions.